Technical Specifications for Greaves Diesel Generator

Sr. No. Genset Rated → 5 kVA (M) 7.5 kVA (M) 10 kVA (M) 15 kVA (M) 20 kVA (M) 25 kVA (M) 30 kVA (M)
A. Genset Specification
1 Genset rating Prime Prime Prime Prime Prime Prime Prime
2 Genset output (kVA/kWe) 5 / 4 7.5 / 6 10 / 8 15 / 12 20 / 16 25 / 20 30 / 24
3 Genset model GPA-PIV-5M GPM-PIV-7.5M GPWII-PIV-10M GPWII-PIV-15M GPWII-PIV-20M GPWII-PIV-25M GPWII-PIV-30M
4 Gross engine Power (kWm)

6.1

8

11

18

18

54.5

54.5

5 Gross engine Power (HP)

8.3

10.9

15

24.5

24.5

74.1

74.1

6 Engine model

LDA 510 181

G 600 W

G12-IV

G20A-IV

G20-IV

3G11TAG31

3G11TAG31

7 Engine type

Mechanical

Mechanical

Mechanical

Mechanical

Mechanical

Mechanical

Mechanical

8

Aspiration/ Cooling

Air cooled

Water cooled

Water cooled

Water cooled

TCAC

TCAC

TCAC

9 No. of Cylinders / Arrangement 1

1

2/inline

2/inline

3/inline

3/inline

3/inline

10 Displacement (L)

0.51

0.612

1.56

1.84

2.34

3.66

3.66

11 Bore x Stroke (mm)

85 X 90

92 X 92

95 X 110

98 X 122

95 X 110

108 X 133

108 X 133

12 Compression ratio

18.1

18.1

17.5

17.5

17.5

16.8

16.8

13 Rated RPM

3000

3000

1500

1500

1500

1500

1500

14 Overspeed trip (RPM)

3300

3300

1650

1650

1650

1650

1650

15 Governor type / DG Perfomance Class

Mech/G2

Mech/G2

Mech/G2

Mech/G2

Mech/G2

Mech/G2(1)

Mech/G2(1)

16 Frequency Regulation     Isochronous

Isochronous

Isochronous

   
17 Air cleaner type/Qty Oil Bath/01

Dry/01

Dry/01

Dry/01

Dry/01

Dry/01

Dry/01

B. Exhaust System
1

Max allowable backpressure before After-treatment (kPa)

5 7.5 7 6.9 7.3 10 10
2

Max allowable backpressure post After-treatment (kPa)

5 5 5 5 5 5 5
3

Exhaust temperature (Deg C)

550 550 550 550 550 450 500
4

Silencer type

Residential

Residential Residential Residential Residential Residential Residential
5

Aftertreatment System

DOC

DOC N/A N/A N/A DOC+POC DOC+POC
C. Engine Electrical System
1

Charging alternator VDC / Amps

N/A 12V/35A 12V/35A 12V/35A 12V/35A 12V/35A 12V/35A
2

Starter motor rated voltage (DC)

12 12 12 13 14 12 12
3

Battery voltage (DC) / Capacity (AH)

12V/35 AH 12V/65 AH 12V/88 AH 12V/88 AH 12V/88 AH 12V/88 AH 12V/88 AH
D. Fuel System
1 Recommended fuel IS 1460, HSD IS 1460, HSD IS 1460, HSD IS 1460, HSD IS 1460, HSD IS 1460, HSD IS 1460, HSD
2 Fuel tank capacity (L) 15 55 30 40 60 60 60
E. Lubricating Oil System
1 Lube oil sump capacity (L)

1.25

1.75

5.5

5.5

6.5

7

7

2

Lube oil change period (Hrs)

300

300

500

500

500

500

500

3

Lube oil consumption (% of SFC)

≤0.1%

≤0.1%

≤0.1%

≤0.1%

≤0.1%

≤0.1%

≤0.1%

4

Lube oil filter type/Qty

Spin on/01

Spin on / 01

Spin on / 01

Spin on / 01

Spin on / 01

Spin on / 01

Spin on / 01

5

Recommended lube oil grade

15W40, API CI4+

15W40, API CI4+

15W40, API CI4+

15W40, API CI4+

15W40, API CI4+

15W40, API CI4+

15W40, API CI4+

6

Recommended lube oil

Greaves Maxtherm

Greaves Maxtherm

Greaves Maxtherm

Greaves Maxtherm

Greaves Maxtherm

Greaves Maxtherm

Greaves Maxtherm

F. Alternator Specification
1 Alternator Make

NSM

NSM

LS

LS

LS

LS

LS

2

Voltage (1P / 3xP)

230/415

230/415

230/415

230/415

230/415

415

415

3

Frequency (Hz)

50

50

50

50

50

50

50

4

Current (1P / 3xP) Amps)

21.79/6.96

32.6/10.43

43.47/13.91 

65.21/20.86

86.95/27.82

34.78

41.73

5

Type

2P, rotating field 2P, rotating field 4P, rotating field 4P, rotating field 4P, rotating field 4P, rotating field 4P, rotating field
6

Voltage regulator

Automatic Automatic Solid state Solid state Automatic Automatic Automatic
7

Voltage regulation -%

±5%

±5%

±1%

±1%

±1%

±1%

±1%

8

Insulation class

H

H

H

H

H

H

H

9

Temperature rise (Deg C)

125

125

125

125

125

125

125

10

Bearing (Qty/type)

1, sealed

1, sealed

1, sealed

1, sealed

1, sealed

1, sealed

1, sealed

11

Coupling

Conical Shaft

Flex disc

Conical Shaft

Conical Shaft

Flex disc

Flex disc

Flex disc

12

Unbalanced load capability

    25% of rated amps 25% of rated amps 25% of rated amps 25% of rated amps 25% of rated amps
G. Cooling System
1 Max ambient capability (Deg C) NA 50 50 50 50 50 50
2

Coolant capacity (Eng + Rad) L)

NA 4 7.5 7.5 11.5 10 10
H. Controller
1

Controller Model

DSE 4520 DSE 4520 DSE 4522 DSE 4522 DSE 4522 DSE 4522MKIII DSE 4522MKIII
I. DEF System
1 Recommended fuel NA NA NA NA NA NA NA
2

DEF Tank Capacity (L)

NA NA NA NA NA NA NA
J. DEF Consumption
1

LPH @ 100%

NA NA NA NA NA NA NA
2

LPH @ 75%

NA NA NA NA NA NA NA

K. Genset Outer Dimensions

1

Length(L) X Width(W) X Height(H) (mm)

1110 x 750 x 863

1600 x 800 x 1050

1420(L) (L-1912 Including Ducts) x 930 x 1285 1420(L) (L-1912 Including Ducts) x 930 x 1285 1650 (1972 Including Ducts) x 930 x 1273

2190 x 1020 x 1710

2190 x 1020 x 1710
2

Dry Weight (Approx.) (kg)

300

400 590 655 805 900 980

Authorised Distributor of