Air Compressor Ludhiana, Jalandhar, Punjab

SMART & SUSTAINABLE POWER SOLUTIONS

Greaves Diesel Generator Supplier India CPCB IV

Compliant Gensets 5 kVA to 5000 kVA

Technical Specifications for Greaves Diesel Generator

Sr. No. Genset Rated → 100kVA (C) 125kVA(M) 125kVA(C) 160kVA(M) 160kVA(C) 180kVA(M) 180kVA(C)
A. Genset Specification
1 Genset rating Prime Prime Prime Prime Prime Prime Prime
2 Genset output (kVA/kWe)

100/80

125/100

125/100

160/128

160/128

180/144 180/144
3 Genset model

GPWII-PIV-10OC

GPWII-PIV-125M

GPWII-PIV-125C

GPW-PIV-160M

GPWII-PIV-160C

GPWI PIV-180M GPWII-PIV-180C
4 Gross engine Power (kWm)

93.2

114

114

144.5

144.5

178.8 178.8
5 Gross engine Power (HP)

126.8

155.1

155,1

196.6

196.6

243.3 243.3
6 Engine model

4611TAG42

4G11TAG31

4611TAG41

6G11TAG32

6G11TAG44

6G11TAG31 6G11TAG42
7 Engine type

CRDI

Mechanical

CRDI

Mechanical

CRDI

Mechanical CRDI
8

Aspiration/ Cooling

TCAC

TCAC

TCAC

TCAC

TCAC TCAC TCAC
9 No. of Cylinders / Arrangement

4/inline

4/inline

4/inline

6/inline

6/inline

6/inline 6/inline
10 Displacement (L)

4.87

4.87

4.87

7.31

7.31

7.31 7.31
11 Bore x Stroke (mm)

108×133

108X133

108X133

108X133

108X133

108X133 108X133
12 Compression ratio

16.8

16.8

16.8

16.8

16.8

16.8 16.8
13 Rated RPM

1500

1500

1500

1500

1500

1500 1500
14 Overspeed trip (RPM)

1650

1650

1650

1650

1650

1650 1650
15 Governor type / DG Perfomance Class

CRS/G3

Elec/G3

CRS/G3

Elec/G3

CRS/G3

Elec/G3 CRS/G3
16 Frequency Regulation

Isochronous

Isochronous Isochronous

Isochronous

Isochronous

Isochronous Isochronous
17 Air cleaner type/Qty

Dry/01

Dry/01

Dry/01

Dry/01

Dry/01

Dry/01 Dry/01
B. Exhaust System
1

Max allowable backpressure before After-treatment (kPa)

10 10 10 13 13 13 13
2

Max allowable backpressure post After-treatment (kPa)

5 5 5 5 5 5 5
3

Exhaust temperature (Deg C)

525 525 525 525 525 530 530
4

Silencer type

NA

NA NA NA NA NA NA
5

Aftertreatment System

DOC+SCR+ASC

DOC+SCR+ASC DOC+SCR+ASC DOC+SCR+ASC DOC+SCR+ASC DOC+SCR+ASC DOC+SCR+ASC
C. Engine Electrical System
1

Charging alternator VDC / Amps

12 V/35 A 12V/35A 12V/35A 12V/35A 12V/35A 12V/35 A 12V/35A
2

Starter motor rated voltage (DC)

12 12 12 12 12 12 12
3

Battery voltage (DC) / Capacity (AH)

12V/88 A AH 12V/88 AH 12V/88 AH 12V/130 AH 12V/130 AH 12V/130 AH 12V/130 AH
D. Fuel System
1 Recommended fuel IS 1460, HSD IS 1460, HSD IS 1460, HSD IS 1460, HSD IS 1460, HSD IS 1460, HSD IS 1460, HSD
2 Fuel tank capacity (L) 200 200 200 260 260 320 320
E. Lubricating Oil System
1 Lube oil sump capacity (L)

10

10

10

17.5

17.5

17.5 17.5
2

Lube oil change period (Hrs)

750

750

750

750

750

750 750
3

Lube oil consumption (% of SFC)

≤0.06%

≤0.06%

≤0.06%

≤0.06%

≤0.06%

≤0.06% ≤0.06%
4

Lube oil filter type/Qty

Spin on/01

Spin on / 01

Spin on / 01

Spin on / 01

Spin on / 01

Spin on/01 Spin on/01
5

Recommended lube oil grade

15W40, API CI4+

15W40, API CI4+

15W40, API CI4+

15W40, API CI4+

15W40, API CI4+

15W40, API CI4+ 15W40, API CI4+
6

Recommended lube oil

Greaves Maxtherm

Greaves Maxtherm

Greaves Maxtherm

Greaves Maxtherm

Greaves Maxtherm

Greaves Maxtherm Greaves Maxtherm
F. Alternator Specification
1 Alternator Make

LS

LS

LS

LS

LS

MECCALTE MECCALTE
2

Voltage (1P / 3P)

415

415

415

415

415

415 415
3

Frequency (Hz)

50

50

50

50

50

50 50
4

Current (1P / 3P) Amps)

139.12

173.9

173.9

222.4

222.4

250.2 250.2
5

Type

4P, rotating field 4P, rotating field 4P, rotating field 4P, rotating field 4P, rotating field 4P, rotating field 4P, rotating field
6

Voltage regulator

Automatic Automatic Automatic Automatic Automatic Automatic Automatic
7

Voltage regulation -%

±1%

±1%

±1%

±1%

±1%

±1% ±1%
8

Insulation class

H

H

H

H

H

H H
9

Temperature rise (Deg C)

125

125

125

125

125

125 125
10

Bearing (Qty/type)

1, sealed

1, sealed

1, sealed

1, sealed

1, sealed

1, sealed 1, sealed
11

Coupling

Flex disc

Flex disc

Flex disc

Flex disc

Flex disc

Flex disc Flex disc
12

Unbalanced load capability

25% of rated amps 25% of rated amps 25% of rated amps 25% of rated amps 25% of rated amps 25% of rated amps 25% of rated amps
G. Cooling System
1 Max ambient capability (Deg C) 50 50 50 50 50 50 50
2

Coolant capacity (Eng + Rad) L)

14 30 30 35 20 35 35
H. Controller
1

Controller Model

DSE 6120 MKIII DSE 6120 MKIII DSE 6120 MKIII DSE 6120 MKIII DSE 6120 MKIII DSE 6120 MKIII DSE 6120 MKIII
I. DEF System
1 Recommended fuel ISO 22241, DIN-70070 ISO 22241, DIN-70070 ISO 22241, DIN-70070 ISO 22241, DIN-70070 ISO 22241, DIN-70070 ISO 22241, DIN-70070 ISO 22241, DIN-70070
2

DEF Tank Capacity (L)

40 40 40 40 40 40 40
J. DEF Consumption
1

LPH @ 100%

1.1 1.4 1.3 1.7 0.8 2.0 1.9
2

LPH @ 75%

0.8 1.1 1.0 1.3 0.6 1.5 1.4

K. Genset Outer Dimensions

1

Length(L) X Width(W) X Height(H) (mm)

3247x1350x 2150

3245x1350x 2150

3245x1350x 2150 4020x1500x2300 4020x1500x2300 4300x1600x2250 4300x1600x2250
2

Dry Weight (Approx.) (kg)

1610

1850 1850 2210 2210 2220 2220

Authorised Distributor of

Scroll to Top